Motor Protective Circuit Breakers(CPKZM) CPKZMO Motor Protective Circuit Breaker is applicable for the circuit of AC50/60Hz, rated insulation voltage 750V, rated operating voltage up to 660V, rated operating current from 0.1A to 25A. It is used for protecting the motor against overload, short-circuit and phase-failure. It can be also used for starting and breaking the starter of motor and for the circuit protection in the circuit of 25A.
Screw or DIN rail mounting Thermal and electromagnetic trip Rated operational current up to 25A Switching capacity 150/50KA/415V Short-circuit release, fixed setting to 14X Iu Single-phasing sensitive With screws or spring loaded terminals Comply with IEC/EN6094
Technical Data
Standard power ratings of 3-phase motors 50/60Hz in category AC-3(kW) |
Setting range of overload tripping current Ir(A) |
Norminal breaking capacity(A) |
Rated operating current 400V Ie(A) |
Reference |
| - |
0.1-0.16 |
100 |
0.16 |
CPKZM0-01 |
| 0.06 |
0.16-0.25 |
100 |
0.25 |
CPKZZM0-02 |
| 0.09 |
0.25-0.4 |
100 |
0.4 |
CPKZM0-03 |
| 0.12 |
0.4-0.63 |
100 |
0.63 |
CPKZM0-04 |
| 0.25 |
0.63-1 |
100 |
1 |
CPKZM0-05 |
| 0.55 |
1-1.6 |
100 |
1.6 |
CPKZM0-06 |
| 0.75 |
1.6-2.5 |
100 |
2.5 |
CPKZM0-07 |
| 1.5 |
2.5-4 |
100 |
4 |
CPKZM0-08 |
| 2.2 |
4-6.3 |
100 |
6.3 |
CPKZM0-10 |
| 3 |
6.3-10 |
100 |
6.6 |
CPKZM0-14 |
| 4 |
6.3-10 |
100 |
10 |
CPKZM0-16 |
| 5.5 |
10-16 |
50 |
16 |
CPKZM0-20 |
| 7.5 |
10-16 |
50 |
16 |
CPKZM0-21 |
| 9 |
16-20 |
50 |
20 |
CPKZM0-22 |
| 12.5 |
20-25 |
50 |
25 |
CPKZM0-32E |
|